Service Hotline
4000-662-888A split structure can be adopted, with the refrigeration unit and the box placed separately
The top of the box is perforated for easy lifting of the motor
Box bottom has 4 support holes sealed with molded silicone plugs to prevent frost & water overflow
The central axis adopts a special sealing device to avoid frosting at low temperatures
Model | LRHS-22.5M-QDC |
Studio Size? (D*W*H)mm | 3000mm×3000mm×2500mm(W×D×H) |
Dimension(D*W*H)mm | 3200mm×3920mm×2780mm(W×D×H) without motor height |
Unit size | 約2600mm×2500mm×2080mm×1 group(W×D×H) without motor height |
Power Cabinet Dimensions | 約1000mm×800mm×2080mm×2 group(W×D×H) without motor height |
Hydrogen system sizing | 約4320mm×2300mm×2080mm(W×D×H) without motor height |
Air System Dimensions | 約5020mm×2500mm×2080mm(W×D×H) without motor height |
Power Cabinet Dimensions | 約800mm×600mm×2080mm×5?group(W×D×H) |
temperature range | -50℃~+100℃【Satisfy static storage requirement】. -40℃~85℃【Meets thermal load requirements, maximum 150kW heat dissipation】. |
|
Humidity range | 10%~95%RH (within the range of 10℃~85℃) [static non-thermal load]. Response time from 10% to 95% RH at 65℃ is less than 100min [Static no thermal load]. Temperature and humidity 60℃/90%RH [Thermal load 150kW]. |
|
Temperature control accuracy | ≤±1℃ [when the engine is not running], ≤±3℃ [when the engine is running, maximum 150kW heat dissipation] | |
Temperature fluctuation | ≤±0.5℃【unladen】、≤±3℃【With load 150KW] | |
Temperature uniformity | ≤2.0℃【When the engine has no heat dissipation in the cabin】 | |
Humidity control accuracy | ±5%RH or less [unladen] | |
Humidity fluctuation | ≤±5%RH【unladen】 | |
heating rate | -40℃~+85℃, the average rate of the whole process is 1℃/min 【Internal 540kg electric pile, heat dissipation 150KW】. | |
cooling rate | +85℃~-40℃, average rate of the whole process 1℃/min [540kg electric pile placed inside, heat dissipation 150KW]. | |
Customer Tested Products | Test Product: Metal-fueled Reactor Engine + Total Weight: 540kg + Reactor Power: 150kw | |
Outer case material | High-quality cold-rolled steel plate (t=1.0mm), surface electrostatic spraying treatment | |
Inner box material | Stainless steel plate (SUS304-CP 2B polished) | |
Base plate material | Non-slip stainless steel plate (SUS304) t=3.0mm welded. Base plate load requirement: more than 2T/mP2 | |
Insulation material | 150mm rigid polyurethane foam insulation layer | |
Lighting lamps | Explosion-proof LED light, with moisture-proof, explosion-proof, transparent, heat insulation, not easy to produce steam frost, etc. | |
Controller | Imported “UEC” brand temperature and humidity meter | |
refrigeration system | Germany “BITZER” semi-hermetic air-cooled / water-cooled compressor refrigeration mode | |
Temperature Controller | High Accuracy Pt100 Platinum Resistance Temperature Sensors | |
Humidity Sensor | Highly accurate Vaisala capacitive humidity sensors from Finland | |
Pressure relief hole | Equipped with an electric pressure balancing device to maintain a slightly positive pressure in the environmental chamber in the range of 0 to 50 Pa under all circumstances. | |
Fans | Single intake multi-blade centrifugal explosion-proof fan with adjustable frequency conversion | |
Secure call system | The box is equipped with a call system to facilitate the call in case of sudden emergencies, which can ensure the safety of the staff inside in emergency situations | |
Optional Accessories | Pump suction explosion-proof hydrogen/oxygen concentration alarm system, fume concentration alarm, access control system, explosion-proof pressure convergence protection device, visualization monitoring system, etc. | |
security protection | Compressor low pressure/overload/high pressure alarm, hydrogen/oxygen/soot concentration alarm, fan overload, system abnormality alarm, emergency stop switch, water shortage, short-circuit, phase shortage, over-temperature and other protections | |
Supply Voltage | AC380V±10% 50Hz | |
Power | Maximum load capacity about 270KW, maximum current: 480A Hydrogen system power about 138KW, maximum current: 240A Air system power about 165KW, maximum current: 290A Total air switch capacity 1500A |