Service Hotline
4000-662-888A split structure can be adopted, with the refrigeration unit and the box placed separately
The top of the box is perforated for easy lifting of the motor
Box bottom has 4 support holes sealed with molded silicone plugs to prevent frost & water overflow
The central axis adopts a special sealing device to avoid frosting at low temperatures
Model | Studio Size? (D*W*H)mm | Dimension(D*W*H)mm | |
LRHS-108-RY | 450×600×400 | 780×1140×1050 | |
LRHS-270-RY | 600×900×500 | 960×1460×1150 | |
LRHS-412-RY | 750×1100×500 | 1100×1730×1240 | |
LRHS-663-RY | 850×1300×600 | 1230×2150×1410 | |
LRHS-816-RY | 850×1600×600 | 1230×2450×1460 | |
LRHS-1080-RY | 900×2000×600 | 1280×2850×1460 |
temperature range | RT+5℃~55℃ | ||||||
Saturated drum temperature | RT+10℃~70℃ | ||||||
Temperature uniformity | ≤2℃ | ||||||
Temperature fluctuation | ±0.5℃ | ||||||
Salt spray deposition | 1~2ml/80 cm2.h(16-hour average) | ||||||
Compressed air pressure | 2.00±0.01(kg/cm2) | ||||||
Spraying method | Continuous/periodic selectable | ||||||
Test time | 1~9999 H、M、S(adjustable) | ||||||
cycle time | 1~99 H、M、S(adjustable) | ||||||
Specimen holder angle | Can meet 15°, 30° tilt test | ||||||
Test Methods | NSS test AASS test CASS test | ||||||
Case Material | Corrosion-resistant, high-strength, anti-aging, high-temperature resistant PP reinforced rigid plastic sheet | ||||||
Lid Material | Corrosion-resistant, high-strength, anti-aging, high-temperature resistant PP reinforced rigid plastic sheet | ||||||
Air-saturated drums | Imported high-grade stainless steel SUS304 | ||||||
Pressurized Air Hose Material | High quality rubber hose | ||||||
Other pipelines | Thickened Fluorosilicone Rubber Tubing | ||||||
Temperature Controller | KEY BOARD Intelligent Integrated Control Temperature Controller | ||||||
temperature sensor | PT100 platinum resistance temperature measurement body | ||||||
heater | Titanium Heating Tube | ||||||
interrupter | Schneider miniature circuit breakers (to prevent short circuits in control circuits) | ||||||
standard configuration | V-shaped sample holders, round rods, nozzles, funnels, metering cylinders, mist evacuation tubes | ||||||
security protection | Over-temperature, overall equipment under-phase/reverse-phase, test timer, rapid fogging instructions Test end, low water level protection, leakage, short circuit |
||||||
Supply Voltage | AC220V±10% 50HZ AC380V±10% 50Hz | ||||||
Power | 1.6kW/2.5kW/3.0kW/5.6kW/6.5kW/6.7kW | ||||||
operating environment | 5℃~+28℃ ≤85% RH | ||||||
Note: 1、 the above data are in the use of ambient temperature of 25 ℃ and well ventilated conditions measured 2、Can be customized according to the specific requirements of the user non-standard salt spray corrosion test chamber etc 3、This technical information, subject to change without notice |