Service Hotline
4000-662-888A split structure can be adopted, with the refrigeration unit and the box placed separately
The top of the box is perforated for easy lifting of the motor
Box bottom has 4 support holes sealed with molded silicone plugs to prevent frost & water overflow
The central axis adopts a special sealing device to avoid frosting at low temperatures
Model | Studio Size? (D*W*H)mm | Dimension(D*W*H)mm | |
LRHS-225-WSZ | 500×600×750 | Subject to contractual three-view | |
LRHS-1000-WSZ | 1000×1000×1000 | ||
LRHS-2000-WSZ | 1000×2000×1000 | ||
LRHS-8000-WSZ | 2000×2000×2000 |
temperature range | -60℃~150℃ | ||||||
Temperature uniformity | ≤2℃ (at no load) | ||||||
Temperature fluctuation | ±0.5℃(at no load) | ||||||
Time Setting Range | 1~60000M | ||||||
Humidity range | 20%~98% RH | ||||||
Humidity uniformity | +2% -3% RH | ||||||
Humidity fluctuations | ±2% | ||||||
heating rate | 1.0~3.0℃/min | ||||||
cooling rate | 0.7~1.0℃/min | ||||||
Lifting platform | Lifting platform method to adjust the height of the test chamber | ||||||
viewing window | 210 x 275mm or 395 x 395mm (effective field of view) | ||||||
sinusoidal thrust | ≥2200kN | ||||||
random thrust | ≥2200kN | ||||||
Impact thrust (6ms) | ≥4400kN | ||||||
frequency range | DC~3000Hz | ||||||
sustained displacement | 45mm(p-p) | ||||||
shock displacement | 45mm(p-p) | ||||||
Maximum speed | 1.5~2.5m/s | ||||||
maximum acceleration | 950m/s2 | ||||||
First order resonant frequency | 2600Hz | ||||||
Allowable eccentricity moment | >500N×m | ||||||
load junction | 16 connections | ||||||
Axial vibration isolation frequency | <3Hz | ||||||
Maximum load | 300kg | ||||||
Countertop Size | 600mm×600mm | ||||||
Maximum load | 300kg | ||||||
Outer case material | High quality A3 steel plate electrostatic spraying | ||||||
Inner box material | Imported high-grade stainless steel SUS304 | ||||||
Insulation material | Rigid polyurethane foam + fiberglass | ||||||
Temperature Controller | Japan’s original imported “UEC” brand temperature meter | ||||||
temperature sensor | PT100 platinum resistance temperature measurement body | ||||||
Cooling method | Two-machine cascade refrigeration | ||||||
Compressor | Tycon (France) / BITZER (Germany) | ||||||
security protection | Compressor overpressure overload, over temperature, fan motor overheating, leakage protection Machine under-phase/reverse-phase, test timing, overload and short circuit protection. |
||||||
Supply Voltage | AC380V±10% 50Hz | ||||||
Power | 24.0kW/48.0kW/60.0kW/85.0kW | ||||||
operating environment | 5℃~+28℃ ≤85% RH | ||||||
Note: 1、 the test data are used in the ambient temperature of 25 ℃ and well ventilated conditions measured 2、Can be customized according to the specific requirements of the?user non-standard three integrated test chamber etc 3、This technical information, subject to change without notice |